Product Details:
Model Name/Number | NA |
Type of VFD | PWM Drives |
Issue | VFD |
We Repair | Yes |
Location | Onsite |
Usage/Application | Industrial |
Product Details:
Model Name/Number | NA |
Type of VFD | PWM Drives |
Issue | VFD |
We Repair | Yes |
Location | Onsite |
Usage/Application | Industrial |
Product Details:
Minimum Order Quantity | 1 Number |
Acceleration And Deceleration Ramps | S, U, Linear from 0 to 999.9 s |
Assembly Style | With Heat Sink |
Continuous Output Current | 2.4 A 4 kHz |
Phase | 1 Phase |
Maximum Transient Current | 3.6 A 60 s |
Minimum Switching Current | 5 mA 24 V DC logic relay |
Product Or Component Type | Variable Speed Drive |
Connector Type | 1 RJ45 Modbus on front face |
Quantity Per Set | Set of 1 |
Transmission Frame | RTU Modbus |
Braking Torque | Up to 70 % of nominal motor torque without braking resistor |
Speed Range | 1 to 20 |
Ambient Air Temperature For Storage | -13 to 158 Deg F (-25 to 70 Deg C) |
Analogue Input Number | 1 |
Analogue Output Number | 1 |
Braking To Standstill | By DC injection Less Than or Equal 30 s |
Component Name | ATV12 |
Discrete Input Number | 4 |
Discrete Output Number | 2 |
Emc Filter | Integrated |
Frequency Resolution | 0.1 Hz display unit, Converter A/D, 10 bits analog input |
Functionality | Basic |
Marking | CE |
Noise Level | 0 dB |
Nominal Switching Frequency | 4 kHz |
Number Of Addresses | 1 to 247 Modbus |
Operating Position | Vertical +/- 10 degree |
Output Voltage | 200 to 240 V 3 phase |
Physical Interface | 2-wire RS 485 Modbus |
Product Destination | Asynchronous Motors |
Product Specific Application | Simple Machine |
Prospective Line Isc | Less Than or Equal 1 kA |
Range Of Product | Altivar 12 |
Specific Application | Commercial Equipment |
Speed Drive Output Frequency | 0.5 to 400 Hz |
Switching Frequency | 2 to 16 kHz adjustable, 4 to 16 kHz with derating factor |
Tightening Torque | 7.08 lbf.in (0.8 N.m) |
Transmission Rate | 4800 bit/s, 9600 bit/s, 19200 bit/s, 38400 bit/s |
Insulation | Electrical between power and control |
IP Degree of Protection | IP20 without blanking plate on upper part |
Built in Fan | Without |
Relative Humidity | 5 to 95 % without condensation IEC 60068-2-3 5 to 95 % without dripping water IEC 60068-2-3 |
Motor Sstarter Type | Variable speed drive |
Shock Resistance | 15 gn EN/IEC 60068-2-27 11 ms |
Discrete Output Type | Logic output LO+, LO /Protected relay output R1A, R1B, R1C 1 C/O |
Line Current | 5.9 A 200 V, 4.9 A 240 V |
Motor Slip Compensation | Preset in factory Adjustable |
Depth | 4.77 in (121.2 mm) |
Transient Overtorque | 150 to 170 % of nominal motor torque depending on drive rating and type of motor |
Electrical Connection | Terminal 3.5 mm2 AWG 12 L1, L2, L3, U, V, W, PA, PC |
Discrete Input Type | Programmable LI1 to LI4 24 V 18 to 30 V |
Model No | ATV12H037M2 |
Motor Power kW | 0.37 |
Supply Frequency | 50/60 Hz +/- 5 % |
Communication Port Protocol | Modbus |
Linearity Error | +/- 0.3 % of maximum value analogue input |
Asynchronous Motor Control Profile | Voltage/Frequency ratio (V/f), Quadratic voltage/frequency ratio, Sensorless flux vector control |
Motor Power HP | 0.55 |
Sampling Duration | 20 ms +/- 1 ms logic input, 10 ms analogue input |
Time Constant | 20 ms +/- 1 ms for reference change |
Product Weight | 1.54 lb(US) (0.7 kg) |
Rated Supply Voltage | 200 to 240 V - 15 to 10 % |
Communication service | Read holding registers (03) 29 words Write single register (06) 29 words Write multiple registers (16) 27 words Read/Write multiple registers (23) 4/4 words Read device identification (43) |
Supply | Internal supply for reference potentiometer 5 V DC 4.75 to 5.25 V 10 mA overload and short-circuit protection Internal supply for logic inputs 24 V DC 20.4 to 28.8 V 100 mA overload and short-circuit protection |
Analogue input type | Configurable voltage AI1 0 to 10 V 30 kOhm Configurable voltage AI1 0 to 5 V 30 kOhm Configurable current AI1 0 to 20 mA 250 Ohm |
Discrete Input Logic | Negative logic (sink) > 16 V < 10 V 3.5 kOhm Positive logic (source) 0 to < 5 V > 11 V |
Analogue output type | Software-configurable voltage AO1 0 to 10 V 470 Ohm 8 bits Software-configurable current AO1 0 to 20 mA 800 Ohm 8 bits |
Maximum Switching current | 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms logic relay 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms logic relay 3 A 250 V AC resistive cos phi = 1 L/R = 0 ms logic relay 4 A 30 V DC resistive cos phi = 1 L/R = 0 ms logic relay |
Protection type | Against input phase loss in three-phase Thermal motor protection via the drive by continuous calculation of I²t Line supply overvoltage Line supply undervoltage Overcurrent between output phases and earth Overheating protection Short-circuit between motor phases |
Discrete and process manufacturing | Commercial equipment : mixer Commercial equipment : other application Textile : ironing |
Electromagnetic compatibility | Immunity to conducted disturbances level 3 EN/IEC 61000-4-6 Surge immunity test level 3 EN/IEC 61000-4-5 Voltage dips and interruptions immunity test EN/IEC 61000-4-11 Electrical fast transient/burst immunity test level 4 EN/IEC 61000-4-4 Electrostatic discharge immunity test level 3 EN/IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3 |
Electromagnetic emission | Radiated emissions environment 1 category C2 EN/IEC 61800-3 2...16 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C1 EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable 5 m Conducted emissions with integrated EMC filter environment 1 category C2 EN/IEC 61800-3 2...12 kHz shielded motor cable 5 m Conducted emissions with integrated EMC filter environment 1 category C2 EN/IEC 61800-3 2, 4 and 16 kHz shielded motor cable 10 m Conducted emissions with additional EMC filter environment 1 category C1 EN/IEC 61800-3 4...12 kHz shielded motor cable 20 m Conducted emissions with additional EMC filter environment 1 category C2 EN/IEC 61800-3 4...12 kHz shielded motor cable 50 m Conducted emmissions with additional EMC filter environment 2 category C3 EN/IEC 61800-3 4 to 12 Khz Shielded motor cable 50 m |
Additional Information:
Product Details:
Assembly Style | With Heat Sink |
Continuous Output Current | 144 A at 12 kHz, 230 V 3 phase |
Maximum Transient Current | 172.8 A for 60 s 3 Phase |
Minimum Switching Current | Configurable relay logic 3 mA at 24 V DC |
Product Or Component Type | Variable Speed Drive |
Transmission Frame | RTU for Modbus |
Regulation Loop | Frequency PI regulator |
Braking Torque | 30 % without braking resistor / Less Than or Equal 125 % with braking resistor |
Speed Accuracy | +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback |
Speed Range | 1 to 100 in open-loop mode, without speed feedback |
Analogue Input Number | 2 |
Analogue Output Number | 1 |
Component Name | ATV61 |
Discrete Input Number | 7 |
Discrete Output Number | 2 |
Emc Filter | Without EMC Filter |
Frequency Resolution | Analog input 0.024/50 Hz / Display unit 0.1 Hz |
Marking | CE |
Network Frequency | 47.5 to 63 Hz |
Noise Level | 64 dB conforming to 86/188/EEC |
Nominal Switching Frequency | 12 kHz |
Operating Position | Vertical +/- 10 degree |
Output Frequency | 0.1 to 599 Hz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Physical Interface | 2-wire RS 485 for Modbus |
Product Destination | Asynchronous motors / Synchronous motors |
Product Specific Application | Pumping and Ventilation Machine |
Prospective Line Isc | 22 kA 3 phases |
Range Of Product | Altivar 61 |
Supply Voltage Limits | 170 to 264 V |
Switching Frequency | 1 to 16 kHz adjustable / 12 to 16 kHz with derating factor |
Torque Accuracy | +/- 15 % in open-loop mode, without speed feedback |
Type Of Polarization | No impedance for Modbus |
Shock Resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Motor Power HP | 50 hp 3 phases at 200 to 240 V |
Model No | ATV61HD37M3X |
Product Weight | 37 Kg |
Synchronous Motor Control Profile | Vector control without sensor, standard |
Isolation | Between power and control terminals |
Network Nnumber of Phase | 3 Phase |
Local Signalling | 1 LED red presence of drive voltage |
Motor Power kW | 37 kW 3 phases at 200 to 240 V |
Ambient Air Temperature for Operation | -10 to 50 Deg C without derating / 50 to 60 Deg C with derating factor |
Ambient Air Ttemperature for Sstorage | -25 to 70 Deg C |
Width | 320 mm |
Transient Overtorque | 130 % of nominal motor torque, +/- 10 % for 60 s |
Method of Access | Slave for CANopen |
Rated Supply Voltage | 200 to 240 V (- 15 to 10 %) |
Supply Frequency | 50 to 60 Hz (- 5 to 5 %) |
Insulation Resistance | Greater Than 1 mOhm at 500 V DC for 1 minute to earth |
Height | 550 mm |
Apparent Power | 52.8 kVA for 240 V 3 phases 37 kW / 50 hp |
Braking to Standstill | By DC injection |
Depth | 266 mm |
Number of Addresses | 1 to 247 for Modbus / 1 to 127 for CANopen |
Asynchronous motor control profile | Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f |
Option card | APOGEE FLN communication card BACnet communication card CC-Link communication card Controller inside programmable card DeviceNet communication card Ethernet/IP communication card Fipio communication card I/O extension card Interbus-S communication card LonWorks communication card METASYS N2 communication card Modbus Plus communication card Modbus TCP communication card Modbus/Uni-Telway communication card Multi-pump card Profibus DP communication card Profibus DP V1 communication card |
Motor slip compensation | Adjustable Automatic whatever the load Can be suppressed Not available in voltage/frequency ratio (2 or 5 points) |
Type of cable | With an IP21 or an IP31 kit : 3-strand IEC cable at 40 °C, copper 70 °C PVC Without mounting kit : 1-strand IEC cable at 45 °C, copper 70 °C PVC Without mounting kit : 1-strand IEC cable at 45 °C, copper 90 °C XLPE/EPR With UL Type 1 kit : 3-strand UL 508 cable at 40 °C, copper 75 °C PVC |
Electrical connection | AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1 to LI6, PWR terminal 2.5 mm² / AWG 14 L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 150 mm² / 300 kcmil |
Tightening torque | L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 41 N.m / 360 lb.in AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1 to LI6, PWR 0.6 N.m |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <= 10 mA for overload and short-circuit protection Internal supply 24 V DC (21 to 27 V), <= 200 mA for overload and short-circuit protection External supply 24 V DC (19 to 30 V) |
Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution 11 bits + sign AI2 software-configurable current 0 to 20 mA, impedance 242 Ohm, resolution 11 bits AI2 software-configurable voltage 0 to 10 V DC, input voltage 24 V max, impedance 30000 Ohm, resolution 11 bits |
Sampling duration | Discrete input LI6 (if configured as logic input) 2 ms, +/- 0.5 ms Analog input AI1-/Al1+ 2 ms, +/- 0.5 ms Analog input Al2 2 ms, +/- 0.5 ms Analog output AO1 2 ms, +/- 0.5 ms Discrete input LI1...LI5 2 ms, +/- 0.5 ms |
Accuracy | AI1-/Al1+ +/- 0.6 % for a temperature variation 60 °C AI2 +/- 0.6 % for a temperature variation 60 °C AO1 +/- 1 % for a temperature variation 60 °C |
Linearity error | AI1-/Al1+ +/- 0.15 % of maximum value AI2 +/- 0.15 % of maximum value AO1 +/- 0.2 % |
Additional Information:
Product Details:
Assembly Style | With Heat Sink |
Continuous Output Current | 7.1 A at 4 kHz |
Maximum Transient Current | 10.7 A for 60 s |
Minimum Switching Current | R1-R2 10 mA at 5 V DC |
Product Or Component Type | Variable Speed Drive |
Connector Type | 1 RJ45 Modbus/CANopen |
Transmission Frame | RTU |
Regulation Loop | Frequency PI Regulator |
Speed Range | 1 to 50 |
Analogue Input Number | 3 |
Analogue Output Number | 1 |
Component Name | ATV312 |
Discrete Input Number | 6 |
Discrete Output Number | 2 |
Emc Filter | Integrated |
Frequency Resolution | Analog input 0.1 to 100 Hz / Display unit 0.1 Hz |
Marking | CE |
Network Frequency | 47.5 to 63 Hz |
Nominal Switching Frequency | 4 kHz |
Operating Position | Vertical +/- 10 degree |
Output Frequency | 0 to 500 kHz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Physical Interface | RS485 multidrop serial link |
Pollution Degree | 2 |
Product Destination | Asynchronous Motors |
Product Specific Application | Simple Machine |
Prospective Line Isc | 5 kA |
Range Of Product | Altivar 312 |
Response Time | AOV, AOC 8 ms for analog / R1A, R1B, R1C, R2A, R2B 8 ms for discrete |
Supply Voltage Limits | 323 to 550 V |
Switching Frequency | 2 to 16 kHz adjustable |
Network Number of Phase | 3 Phase |
Linearity Error | +/- 0.2 % for output |
Height | 184 mm |
Insulation | Electrical between power and control |
Model No | ATV312HU30N4 |
Product Weight | 3.1 kg |
Depth | 152 mm |
Outer Dimension | 184 x 140 x 150, 215 x 185 x 158, 402 x 239 x 192 mm |
Width | 142 mm |
Line Current | 10.9 A for 380 V, 5 kA / 8.3 A for 500 V |
Shock Resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Ambient Air Temperature for Storage | -25 to 70 Deg C |
Discrete Input Type | (LI1 to LI6) programmable, 24 V 0 to 100 mA with PLC, impedance 3500 Ohm |
Transient Overtorque | 170 to 200 % of nominal motor torque |
Apparent Power | 7.1 kVA |
Communication Port Protocol | CANopen Modbus |
Number of Addresses | 1 to 247 Modbus / 1 to 127 CANopen |
Time Constant | 5 ms for reference change |
Protective Treatment | TC |
Number of Drive | 127 CANopen / 31 Modbus |
Braking to Standstil | By DC injection |
Power Dissipation | 125 W at Nominal Load |
Sampling Duration | AI1, AI2, AI3 8 ms for analog / LI1 to LI6 4 ms for discrete |
Asynchronous motor control profile | Factory set : constant torque Sensorless flux vector control with PWM type motor control signal |
Electrical connection | L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 5 mm?? AWG 10 Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm?? AWG 14 |
Supply | Internal supply for logic inputs at 19...30 V, <= 100 mA for overload and short-circuit protection Internal supply for reference potentiometer (2.2 to 10 kOhm) at 10...10.8 V, <= 10 mA for overload and short-circuit protection |
IP degree of protection | IP20 on upper part without cover plate IP21 on connection terminals IP31 on upper part IP41 on upper part |
Option card | CANopen daisy chain communication card DeviceNet communication card Fipio communication card Modbus TCP communication card Profibus DP communication card |
Braking torque | 100 % with braking resistor continuously 150 % without braking resistor 150 % with braking resistor for 60 s |
Motor slip compensation | Adjustable Automatic whatever the load Suppressable |
Tightening torque | 1.2 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- 0.6 N.m Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1 to LI6 |
Analogue input type | AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance 30000 Ohm AI3 configurable current 0...20 mA, impedance 250 Ohm |
Sampling duration | AI1, AI2, AI3 8 ms for analog LI1...LI6 4 ms for discrete |
Analogue output type | AOC configurable current 0...20 mA, impedance 800 Ohm, resolution 8 bits AOV configurable voltage 0...10 V, impedance 470 Ohm, resolution 8 bits |
Discrete input logic | (LI1...LI4) logic input not wired, < 13 V (state 1) (LI1...LI6) negative logic (source), > 19 V (state 0) (LI1...LI6) positive logic (source), < 5 V (state 0), > 11 V (state 1) |
Discrete output type | (R1A, R1B, R1C) configurable relay logic 1 NO + 1 NC, electrical durability 100000 cycles (R2A, R2B) configurable relay logic NC, electrical durability 100000 cycles |
Maximum switching current | R1-R2 on inductive load, 2 A at 250 V AC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on inductive load, 2 A at 30 V DC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on resistive load, 5 A at 250 V AC, (cos phi = 1, and L/R = 0 ms) R1-R2 on resistive load, 5 A at 30 V DC, (cos phi = 1, and L/R = 0 ms) |
Acceleration and deceleration ramps | Linear adjustable separately from 0.1 to 999.9 s S, U or customized |
Additional Information:
Product Details:
Brand | Schneider |
Assembly Style | With Heat Sink |
Phase | 3 Phase |
Maximum Transient Current | 41.6 A 60 s 11 kW 15 hp |
Minimum Switching Current | 5 mA 24 V DC configurable relay logic |
Product Or Component Type | Variable Speed Drive |
Connector Type | 1 RJ45 Modbus/CANopen on front face |
Regulation Loop | Adjustable PID Regulator |
Transmission Frame | RTU Modbus |
Braking Torque | Less Than or Equal 170 % with braking resistor |
Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Speed Range | 1 to 100 asynchronous motor in open-loop mode |
Analogue Input Number | 3 |
Analogue Output Number | 1 |
Component Name | ATV32 |
Discrete Input Number | 7 |
Discrete Output Number | 3 |
Emc Filter | Class C2 EMC filter integrated |
Functionality | Mid |
Marking | CE |
Network Frequency | 47.5 to 63 Hz |
Noise Level | 43 dB 86/188/EEC |
Nominal Switching Frequency | 4 kHz |
Operating Position | Vertical +/- 10 Degree |
Output Frequency | 0.0005 to 0.599 kHz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Physical Interface | 2-wire RS 485 Modbus |
Pollution Degree | 2 EN/IEC 61800-5-1 |
Product Destination | Asynchronous Motors, Synchronous Motors |
Product Specific Application | Complex Machines |
Prospective Line Isc | Less Than or Equal 22 kA 3 phases |
Range Of Product | Altivar 32 |
Response Time | 8 ms +/- 0.7 ms LI1 to LI6 logic / 2 ms R1A, R1B, R1C relay / 2 ms R2A, R2C relay |
Supply Voltage Limits | 323 to 550 V |
Switching Frequency | 2 to 16 kHz adjustable |
Torque Accuracy | +/- 15 % |
Transient Overtorque | 170 to 200 % |
Linearity Error | +/- 0.2 to 0.5 % of maximum value AI1, AI2, AI3, +/- 0.3 % AO1 |
Rated Supply Voltage | 380 to 500 V - 15 to 10 % |
IP Degree of Protection | IP20 EN/IEC 61800-5-1 |
Braking to Standstill | By DC injection |
Method of Access | Slave CANopen |
Relative Humidity | 5 to 95 % without condensation IEC 60068-2-3 5 to 95 % without dripping water IEC 60068-2-3 |
Width | 7.09 in (180 mm) |
Vibration Resistance | 1 gn 13 to 200 Hz EN/IEC 60068-2-6, 1.5 mm peak to peak 3 to 13 Hz EN/IEC 60068-2-6 |
Type of Polarization | No Impedance Modbus |
Insulation | Electrical between power and control |
Product Weight | 19.18 lb(US) (8.7 kg) |
Sampling Duration | 2 ms AI1, AI2, AI3 analog, 2 ms AO1 analog |
Motor Power kW | 11 kW 380 to 480 V |
Ambient air Temperature For Storage | -13 to 158 Deg F (-25 to 70 Deg C) |
Number of Addresses | 1 to 247 Modbus, 1 to 127 CANopen |
Motor Power | 15 hp 380 to 480 V |
Model No | ATV32HD11N4 |
Supply Frequency | 50 to 60 Hz - 5 to 5 % |
Synchronous Motor Control Profile | Vector control without sensor |
Line Current | 25.6 A 500 V 3 phases 11 kW 15 hp, 36.6 A 380 V 3 phases 11 kW 15 hp |
Height | 15.91 in (404 mm) |
Nominal Output Current | 27.7 A 4 kHz 500 V 11 kW 15 hp |
Shock Resistance | 15 gn 11 ms EN/IEC 60068-2-27 |
Communication Port Protocol | CANopen, Modbus |
Apparent Power | 31.7 kVA 500 V 3 phases 15 kW 20 hp |
We offer Schneider Altivar 32 Drives VFD to our clients.
Technical Specifications:
Asynchronous motor control profile | Voltage/Frequency ratio, 2 points Flux vector control without sensor, standard Voltage/Frequency ratio, 5 points Voltage/Frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving, NoLoad law |
Motor slip compensation | Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Adjustable 0 to 300 % |
Local signalling | 1 LED green CANopen run 1 LED red CANopen error 1 LED red drive fault 1 LED red drive voltage |
Electrical connection | Screw terminal 0.5...1.5 mm² AWG 18...AWG 14 control Removable screw terminals 6...16 mm² AWG 8...AWG 6 motor/braking resistor Screw terminal 10...16 mm² AWG 8...AWG 6 power supply |
Tightening torque | 4.42 lbf.in (0.5 N.m) 4.4 lb/ft control 10.62 lbf.in (1.2 N.m) 10.6 lb/ft motor/braking resistor 10.62 lbf.in (1.2 N.m) 10.6 lb/ft power supply |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 mA overload and short-circuit protection |
Analogue input type | Voltage AI1 0...10 V DC 30000 Ohm 10 bits Bipolar differential voltage AI2 +/- 10 V DC 30000 Ohm 10 bits Current AI3 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 Bits |
Accuracy | +/- 0.2 % AI1, AI2, AI3 for a temperature of -10...60 °C +/- 0.5 % AI1, AI2, AI3 for a temperature of 25 °C +/- 1 % AO1 for a temperature of 25 °C +/- 2 % AO1 for a temperature of -10...60 °C |
Analogue output type | Software-configurable current AO1 0...20 mA 800 Ohm 10 bits Software-configurable voltage AO1 0...10 V 470 Ohm 10 bits |
Discrete output type | Configurable relay logic R1A, R1B, R1C NO/NC 100000 cycles Configurable relay logic R2A, R2B NO 100000 cycles Logic LO |
Maximum switching current | 3 A 250 V AC resistive (cos phi = 1 R1 4 A 30 V DC resistive (cos phi = 1 R1 2 A 250 V AC inductive (cos phi = 0.4 R1, R2 2 A 30 V DC inductive (cos phi = 0.4 R1, R2 5 A 250 V AC resistive (cos phi = 1 R2 5 A 30 V DC resistive (cos phi = 1 R2 |
Discrete input type | Programmable (sink/source) LI1...LI4 24...30 V DC level 1 PLC Programmable as pulse input 20 kpps LI5 24...30 V DC level 1 PLC Switch-configurable PTC probe LI6 24...30 V DC Safe torque off STO 24...30 V DC 1500 Ohm |
Discrete input logic | Negative logic (sink) LI1...LI6 > 19 V < 13 V Positive logic (source) LI1...LI6 < 5 V > 11 V |
Additional Information:
Product Details:
Transmission Frame | RTU |
Dielectric Strength | 2410 V DC between earth and power terminals / 3400 V AC between control and power terminals |
Brand | Schneider |
Motor Power | 2 HP |
Output Frequency | 0 to 500 kHz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Rated Supply Voltage | 380 to 500 V (- 15 to 10 %) |
Supply Voltage Limits | 323 to 550 V |
Supply Frequency | 50 to 60 Hz (- 5 to 5 %) |
Insulation Resistance | Greater Than or Equal 500 mOhm at 500 V DC for 1 minute |
Motor Power kW | 1.5 |
Network Number of Phase | 3 phase |
Discrete Input Type | (LI1 to LI6) programmable, 24 V 0 to 100 mA with PLC, impedance 3500 Ohm |
Model No | ATV312HU15N4 |
Operating Altitude | Less Than or Equal 1000 m without derating / 1000 to 3000 m with current derating 1 % per 100 m |
Sampling Duration | AI1, AI2, AI3 8 ms for analog / LI1 to LI6 4 ms for discrete |
Number of Drive | 127 CANopen, 31 Modbus |
Local Signalling | 1 LED red for drive voltage, Four 7-segment display units for CANopen bus status |
Line Current | 6.4 A for 380 V, 5 kA / 4.8 A for 500 V |
Power Dissipation | 61 W at nominal load |
Depth | 152 mm |
Shock Resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Apparent Power | 4.2 kVA |
Motor Slip Compensation | Adjustable, Automatic whatever the load, Suppressable |
Communication Port Protocol | CANopen Modbus |
Insulation | Electrical between power and control |
Time Constant | 5 ms for reference change |
Asynchronous Motor Control Profile | Factory set constant torque, Sensorless flux vector control with PWM type motor control signal |
Transient Overtorque | 170 to 200 % of nominal motor torque |
Protective Treatment | TC |
Outer Dimension | 143 x 105 x 150, 184 x 149 x 157, 382 x 239 x 170 mm |
Linearity Error | +/- 0.2 % for output |
Product Weight | 1.8 Kg |
Electrical connection | L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 5 mm² AWG 10 Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm² AWG 14 |
Supply | Internal supply for logic inputs at 19...30 V, <= 100 mA for overload and short-circuit protection Internal supply for reference potentiometer (2.2 to 10 kOhm) at 10...10.8 V, <= 10 mA for overload and short-circuit protection |
IP degree of protection | IP20 on upper part without cover plate IP21 on connection terminals IP31 on upper part IP41 on upper part |
Option card | CANopen daisy chain communication card DeviceNet communication card Fipio communication card Modbus TCP communication card Profibus DP communication card |
Braking torque | 100 % with braking resistor continuously 150 % without braking resistor 150 % with braking resistor for 60 s |
Tightening torque | 1.2 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- 0.6 N.m Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1 to LI6 |
Analogue input type | AI1 configurable voltage 0 to 10 V, input voltage 30 V max, impedance 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance 30000 Ohm AI3 configurable current 0 to 20 mA, impedance 250 Ohm |
Analogue output type | AOC configurable current 0 to 20 mA, impedance 800 Ohm, resolution 8 bits AOV configurable voltage 0 to 10 V, impedance 470 Ohm, resolution 8 bits |
Discrete input logic | (LI1 to LI4) logic input not wired, < 13 V (state 1) (LI1 to LI6) negative logic (source), > 19 V (state 0) (LI1 to LI6) positive logic (source), < 5 V (state 0), > 11 V (state 1) |
Discrete output type | (R1A, R1B, R1C) configurable relay logic 1 NO + 1 NC, electrical durability 100000 cycles (R2A, R2B) configurable relay logic NC, electrical durability 100000 cycles |
Maximum switching current | R1-R2 on inductive load, 2 A at 250 V AC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on inductive load, 2 A at 30 V DC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on resistive load, 5 A at 250 V AC, (cos phi = 1, and L/R = 0 ms) R1-R2 on resistive load, 5 A at 30 V DC, (cos phi = 1, and L/R = 0 ms) |
Protection type | Input phase breaks drive Line supply overvoltage and undervoltage safety circuits drive Line supply phase loss safety function, for three phases supply drive Motor phase breaks drive Overcurrent between output phases and earth (on power up only) drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor |
Transmission rate | 10, 20, 50, 125, 250, 500 kbps or 1 Mbps CANopen 4800, 9600 or 19200 bps Modbus |
Additional Information:
Product Details:
Depth | 5.98 in (152 mm) |
Discrete Input Type | (LI1 to LI6) programmable, 24 V 0...100 mA with PLC, impedance 3500 Ohm |
Linearity Error | +/- 0.2 % output |
Height | 7.24 in (184 mm) |
Motor Power kW | 2.2 |
Width | 5.59 in (142 mm) |
Line Current | 18.4 Afor 240 V / 21.9 Afor 200 V, 1 kA |
Insulation | Electrical between power and control |
Motor Slip Compensation | Adjustable, Automatic whatever the loadn, Suppressable |
Sampling Duration | AI1, AI2, AI3 8 ms analog / LI1 to LI6 4 ms discrete |
Model No | ATV312HU22M2 |
Standards | IEC 61800-3, IEC 61800-5-1 |
Power Dissipation | 123 W at nominal load |
Asynchronous Motor Control Profile | Factory set constant torque Sensorless flux vector control with PWM type motor control signal |
Communication Port Protocol | CANopen, Modbus |
Number of Drive | 127 CANopen / 31 Modbus |
Outer Dimension | 184 x 140 x 150, 215 x 185 x 158, 230 x 200 x 152 mm |
Shock Resistance | 15 gn 11 ms conforming to EN/IEC 60068-2-27 |
Apparent Power | 4.4 kVA |
Transient Overtorque | 170 to 200 % of nominal motor torque |
Local Signalling | 1 LED red drive voltage, Four 7-segment display units CANopen bus status |
Time Constant | 5 ms for reference change |
Electrical connection | L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 0.01 in² (5 mm²) AWG 10 Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1 to LI6 terminal 0 in² (2.5 mm²) AWG 14 |
Supply | Internal supply for logic inputsat 19 to 30 V, <= 100 mAfor overload and short-circuit protection Internal supply for reference potentiometer (2.2 to 10 kOhm)at 10 to 10.8 V, <= 10 mAfor overload and short-circuit protection |
IP degree of protection | IP20 on upper part without cover plate IP21 on connection terminals IP31 on upper part IP41 on upper part |
Option card | CANopen daisy chain communication card DeviceNet communication card Fipio communication card Modbus TCP communication card Profibus DP communication card |
Braking torque | 100 % with braking resistor continuously 150 % without braking resistor 150 % with braking resistor for 60 s |
Tightening torque | 10.62 lbf.in (1.2 N.m) L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- 5.31 lbf.in (0.6 N.m) Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1 to LI6 |
Analogue input type | AI1 configurable voltage 0 to 10 V, input voltage 30 V max, impedance 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance 30000 Ohm AI3 configurable current 0 to 20 mA, impedance 250 Ohm |
Analogue output type | AOC configurable current 0...20 mA, impedance 800 Ohm, resolution 8 bits AOV configurable voltage 0...10 V, impedance 470 Ohm, resolution 8 bits |
Discrete input logic | (LI1 to LI4) logic input not wired, < 13 V (state 1) (LI1 to LI6) negative logic (source), > 19 V (state 0) (LI1 to LI6) positive logic (source), < 5 V (state 0), > 11 V (state 1) |
Discrete output type | (R1A, R1B, R1C) configurable relay logic 1 NO + 1 NC, electrical durability 100000 cycles (R2A, R2B) configurable relay logic NC, electrical durability 100000 cycles |
Maximum switching current | R1-R2 on inductive load, 2 A at 250 V AC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on inductive load, 2 A at 30 V DC, (cos phi = 0.4, and L/R = 7 ms) R1-R2 on resistive load, 5 A at 250 V AC, (cos phi = 1, and L/R = 0 ms) R1-R2 on resistive load, 5 A at 30 V DC, (cos phi = 1, and L/R = 0 ms) |
Protection type | Input phase breaks drive Line supply overvoltage and undervoltage safety circuits drive Line supply phase loss safety function, for three phases supply drive Motor phase breaks drive Overcurrent between output phases and earth (on power up only) drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor |
Additional Information:
Product Details:
Minimum Switching Current | Configurable relay logic 3 mA at 24 V DC |
Transmission Frame | RTU for Modbus |
Analogue Output Number | 1 |
Discrete Input Number | 7 |
Discrete Output Number | 2 |
Frequency Resolution | Analog input 0.024/50 Hz, Display unit 0.1 Hz |
Marking | CE |
Operating Position | Vertical +/- 10 degree |
Physical Interface | 2-wire RS 485 for Modbus |
Shock Resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Operating Altitude | Less Than or Equal 1000 m without derating, 1000 to 3000 m with current derating 1 % per 100 m |
Linearity Error | AI1-/Al1+, AI2 +/- 0.15 % of maximum value, AO1 +/- 0.2 % |
Insulation | Electrical between power and control |
Width | 130 mm |
Number of Addresses | 1 to 247 for Modbus, 1 to 127 for CANopen |
Local Signalling | 1 LED red presence of drive voltage |
Depth | 175 mm |
Method of Access | Slave for CANopen |
Nominal Output Current | 3 A at 4 kHz 230 V 3 phases 0.37 kW / 0.5 hp |
Synchronous Motor Control Profile | Vector control without speed feedback |
Model No | ATV71H037M3 |
Apparent Power | 1.3 kVA at 240 V 3 phases 0.37 kW / 0.5 hp |
Network Number of Phase | 3 phase |
Product Weight | 3 Kg |
Height | 230 mm |
Ambient Air Temperature for Operation | -10 to 50 Deg C without derating |
Motor Power HP | 0.5 hp at 200 to 240 V 3 phase |
Communication Port Protocol | CANopen Modbus |
Insulation Resistance | Greater Than 1 mOhm at 500 V DC for 1 minute to earth |
Line Current | 3.1 A for 240 V 3 phases 0.37 kW / 0.5 hp, 3.5 A for 200 V 3 phases 0.37 kW / 0.5 hp |
Motor cable length | <= 50 m Shielded cable <= 100 m Unshielded cable |
Asynchronous motor control profile | ENA (Energy adaptation) system for unbalanced loads Flux vector control (FVC) with sensor (current vector) Sensorless flux vector control (SFVC) (voltage or current vector) Voltage/Frequency ratio (2 or 5 points) |
Product destination | Asynchronous motors Synchronous motors |
Speed range | 1 to 100 for asynchronous motor in open-loop mode, without speed feedback 1 to 50 for synchronous motor in open-loop mode, without speed feedback 1 to 1000 for asynchronous motor in closed-loop mode with encoder feedback |
Speed accuracy | +/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode with encoder feedback +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback |
Transient Overtorque | 220 % of nominal motor torque +/- 10 % for 2 s 170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes |
Motor slip compensation | Adjustable Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Suppressable |
Type of cable | With a NEMA Type1 kit : 3-strand UL 508 cable at 40 ??C, copper 75 ??C PVC With an IP21 or an IP31 kit : 3-strand IEC cable at 40 ??C, copper 70 ??C PVC Without mounting kit : 1-strand IEC cable at 45 ??C, copper 70 ??C PVC Without mounting kit : 1-strand IEC cable at 45 ??C, copper 90 ??C XLPE/EPR |
Electrical connection | AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5 mm?? / AWG 14 L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 4 mm?? / AWG 10 |
Tightening torque | AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 0.6 N.m L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 1.4 N.m / 12.3 lb.in |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm), 10.5 V DC +/- 5 %, <= 10 mA for overload and short-circuit protection Internal supply, 24 V DC, voltage limits 21...27 V, <= 200 mA for overload and short-circuit protection |
Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution 11 bits + sign AI2 software-configurable current 0...20 mA, impedance 242 Ohm, resolution 11 bits AI2 software-configurable voltage 0...10 V DC, input voltage 24 V max, impedance 30000 Ohm, resolution 11 bits |
Sampling duration | AI1-/Al1+ 2 ms, +/- 0.5 ms for analog input(s) Al2 2 ms, +/- 0.5 ms for analog input(s) LI1...LI5 2 ms, +/- 0.5 ms for discrete input(s) LI6 (if configured as logic input) 2 ms, +/- 0.5 ms for discrete input(s) |
Additional Information:
Product Details:
Assembly Style | With Heat Sink |
Phase | 3 Phases |
Maximum Transient Current | 109 Afor 2 s 3 phases 15 kW / 20 hp, 99 Afor 60 s 3 phases 15 kW / 20 hp |
Minimum Switching Current | Configurable relay logic 3 mAat 24 V DC |
Product Or Component Type | Variable Speed Drive |
Connector Type | 1 RJ45 Modbus on front face 1, RJ45 Modbus on terminal Male, SUB-D 9 on RJ45 CANopen |
Transmission Frame | RTU Modbus |
Regulation Loop | Adjustable PI Regulator |
Braking Torque | Less Than or Equal 150 % with braking or hoist resistor 30 % without braking resistor |
Analogue Output Number | 1 |
Component Name | ATV71 |
Discrete Input Number | 7 |
Discrete Output Number | 2 |
Emc Filter | Without EMC Filter |
Frequency Resolution | Analog input 0.024/50 Hz, Display unit 0.1 Hz |
Marking | CE |
Network Frequency | 47.5 to 63 Hz |
Noise Level | 60.2 dB conforming to 86/188/EEC |
Nominal Switching Frequency | 4 kHz |
Operating Position | Vertical +/- 10 degree |
Output Frequency | 0.1 to 599 Hz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Physical Interface | 2-wire RS 485 Modbus |
Pollution Degree | 2 conforming to EN/IEC 61800-5-1 |
Product Destination | Asynchronous Motors, Synchronous Motors |
Product Specific Application | Complex, high-power machines |
Prospective Line Isc | Less Than or Equal 22 kA, 3 phases |
Range Of Product | Altivar 71 |
Supply Voltage Limits | 170 to 264 V |
Switching Frequency | 1 to 16 kHz adjustable, 4 to 16 kHz with derating factor |
Torque Accuracy | +/- 15 % in open-loop mode, without speed feedback +/- 5 % in closed-loop mode with encoder feedback |
Type Of Polarization | No impedance Modbus |
Depth | 8.39 in (213 mm) |
Motor Power | 20 hpat 200 to 240 V 3 phases |
Ambient Air Temperature for Storage | -13 to 158 Deg F (-25 to 70 Deg C) |
Standards | IEC 60721-3-3 class 3C1, IEC 60721-3-3 class 3S2, UL Type 1 |
Number of Addresses | 1 to 247 Modbus 1 to 127 CANopen |
Synchronous Motor Control Profile | Vector control without speed feedback |
Width | 48.5 lb(US) (22 kg) |
Insulation | Electrical between power and control |
Dielectric Strength | 2830 V DC between earth and power terminals, 4230 V DC between control and power terminals |
Height | 15.75 in (400 mm) |
Braking to Standstill | By DC injection |
Communication Port Protocol | CANopen, Modbus |
Line Current | 61.6 Afor 240 V 3 phases 15 kW / 20 hp, 71.7 Afor 200 V 3 phases 15 kW / 20 hp |
Rated Supply Voltage | 200 to 240 V (- 15 to 10 %) |
Apparent Power | 25.6 kVAat 240 V 3 phases 15 kW / 20 hp |
Insulation Resistance | Greater Than 1 mOhm at 500 V DC for 1 minute to earth |
Analogue Input Nnumber | 2 |
Shock Resistance | 15 gn 11 ms conforming to EN/IEC 60068-2-27 |
Method of Access | Slave CANopen |
Supply Frequency | 50 to 60 Hz (- 5 to 5 %) |
Ambient Air Temperature for Operation | 14 to 122 Deg F (-10 to 50 Deg C) without derating |
Nominal Output Current | 66 Aat 4 kHz 230 V 3 phases 15 kW / 20 hp |
Model No | ATV71HD15M3X |
Local Signalling | 1 LED red presence of drive voltage |
Motor Power kW | 15 kWat 200 to 240 V 3 phases |
Motor cable length | <= 164.04 ft (50 m) Shielded cable <= 328.08 ft (100 m) Unshielded cable |
Asynchronous motor control profile | ENA (Energy adaptation) system for unbalanced loads Flux vector control (FVC) with sensor (current vector) Sensorless flux vector control (SFVC) (voltage or current vector) Voltage/Frequency ratio (2 or 5 points) |
Speed range | 1 to 100 asynchronous motor in open-loop mode, without speed feedback 1 to 50 synchronous motor in open-loop mode, without speed feedback 1 to 1000 asynchronous motor in closed-loop mode with encoder feedback |
Speed accuracy | +/- 0.01 % of nominal speed 0.2 Tn to Tn torque variation in closed-loop mode with encoder feedback +/- 10 % of nominal slip 0.2 Tn to Tn torque variation without speed feedback |
Transient overtorque | 220 % of nominal motor torque +/- 10 %for 2 s 170 % of nominal motor torque +/- 10 %for 60 s every 10 minutes |
Motor Slip Compensation | Adjustable Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Suppressable |
Type of cable | With a NEMA Type1 kit: 3-strand UL 508 cableat 104 °F (40 °C), copper 75 °C PVC With an IP21 or an IP31 kit: 3-strand IEC cableat 104 °F (40 °C), copper 70 °C PVC Without mounting kit: 1-strand IEC cableat 113 °F (45 °C), copper 70 °C PVC Without mounting kit: 1-strand IEC cableat 113 °F (45 °C), copper 90 °C XLPE/EPR |
Electrical connection | AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1 to LI6, PWR terminal 2.5 mm² / AWG 14 L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 35 mm² / AWG 2 |
Tightening torque | AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1 to LI6, PWR 5.31 lbf.in (0.6 N.m) L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 47.79 lbf.in (5.4 N.m) / 47.7 lb.in |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm), 10.5 V DC +/- 5 %, <= 10 mAfor overload and short-circuit protection Internal supply, 24 V DC, voltage limits 21 to 27 V, <= 200 mAfor overload and short-circuit protection |
Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution 11 bits + sign AI2 software-configurable current 0 to 20 mA, impedance 242 Ohm, resolution 11 bits AI2 software-configurable voltage 0 to 10 V DC, input voltage 24 V max, impedance 30000 Ohm, resolution 11 bits |
Sampling duration | AI1-/Al1+ 2 ms, +/- 0.5 ms analog input(s) Al2 2 ms, +/- 0.5 ms analog input(s) LI1 to LI5 2 ms, +/- 0.5 ms discrete input(s) LI6 (if configured as logic input) 2 ms, +/- 0.5 ms discrete input(s) |
Additional Information:
Product Details:
Brand | Schneider |
Assembly Style | With Heat Sink |
Maximum Transient Current | 6.2 A for 60 s |
Minimum Switching Current | R1-R2 10 mA at 5 V DC |
Product Or Component Type | Variable Speed Drive |
Regulation Loop | Frequency PI regulator |
Speed Range | 1.50 |
Analogue Input Number | 3 |
Height | 143 mm |
Analogue Output Number | 1 |
Width | 107 mm |
Component Name | ATV312 |
Discrete Input Number | 6 |
Discrete Output Number | 2 |
Emc Filter | Integrated |
Marking | CE |
Network Frequency | 47.5 to 63 Hz |
Nominal Switching Frequency | 4 kHz |
Number Of Addresses | 1 to 247 Modbus, 1 to 127 CAN open |
Operating Position | Vertical +/- 10 degree |
Output Frequency | 0.500 kHz |
Output Voltage | Less Than or Equal Power Supply Voltage |
Pollution Degree | 2 |
Product Destination | Asynchronous Motors |
Product Specific Application | Simple Machine |
Prospective Line Isc | 5 kA |
Range Of Product | Altivar 312 |
Response Time | AOV, AOC 8 ms for analog, R1A, R1B, R1C, R2A, R2B 8 ms for discrete |
Supply Voltage Limits | 323 to 550 V |
Switching Frequency | 2.16 kHz Adjustable |
Apparent Power | 4.2 kVA |
Communication Port Protocol | CANopen Modbus |
Operating Altitude | Less Than or Equal 1000 m without derating, 1000 to 3000 m with current derating 1 % per 100 m |
Outer Dimension | 143 x 105 x 150, 184 x 149 x 157, 382 x 239 x 170 mm |
Dielectric Strength | 2410 V DC between earth and power terminals, 3400 V AC between control and power terminals |
Braking to Standstill | By DC injection |
Ambient Air Temperature for Storage | -25.70 Deg C |
Local Signalling | 1 LED red for drive voltage, Four 7-segment display units for CANopen bus status |
Asynchronous Motor Control Profile | Factory set constant torque Sensorless flux vector control with PWM type motor control signal |
Power Dissipation | 61 W at Nominal Load |
Shock Resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Acceleration and Deceleration Ramps | Linear adjustable separately from 0.1 to 999.9 s S, U |
Transient Overtorque | 170 to 200 % of nominal motor torque |
Line Current | 6.4 A for 380 V, 5 kA 4.8 A for 500 V |
Depth | 152 mm |
Network Number of Phases | 3 Phases |
Supply Frequency | 50.60 Hz (- 5.5 %) |
Rated Supply Voltage | 380 to 500 V (- 15.10 %) |
Insulation | Electrical Between Power and Control |
Motor Power | 1.5 kW |
Protective Treatment | TC |
Standards | IEC 61800-3, IEC 61800-5-1 |
Product Weight | 1.8 kg |
Linearity Error | +/- 0.2 % for Output |
Discrete Input Type | (LI1 to LI6) programmable, 24 V 0 to 100 mA with PLC, impedance 3500 Ohm |
Continuous Output Curren | 4.1 A at 4 kHz |
Insulation Resistance | Less Than or Equal 500 mOhm at 500 V DC for 1 minute |
Sampling Duration | AI1, AI2, AI3 8 ms for analog, LI1.LI6 4 ms for discrete |
Motor Slip Compensation | Adjustable, Automatic whatever the load, Suppressable |
Motor Power HP | 2 |
Number of Drive | 127 CANopen, 31 Modbus |
We offer SchneiderAltivar ATV312HU15N4-VFD to our clients.
Technical Specifications:
Additional Information:
Product Details:
Acceleration And Deceleration Ramps | Automatic based on the load, Linear adjustable separately from 0.01 to 3200 s |
Assembly Style | With Heat Sink |
Continuous Output Current | 88 A 230 V |
Ip Degree Of Protection | IP21 |
Maximum Transient Current | 96.8 A 60 s |
Minimum Switching Current | 3 mA 24 V DC configurable relay logic |
Product Or Component Type | Variable Speed Drive |
Connector Type | 1 RJ45, 1 open style |
Regulation Loop | Adjustable PI Regulator |
Transmission Frame | RTU |
Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Speed Range | 1 to 10 |
Air Flow | 261 m3/h |
Ambient Air Temperature For Storage | -25 to 70 Deg C |
Analogue Input Number | 2 |
Analogue Output Number | 1 |
Braking To Standstill | By DC injection |
Data Format | 8 bits, 1 stop, odd even or no configurable parity |
Device Short Name | ATV212 |
Discrete Output Number | 2 |
Emc Filter | Without EMC Filter |
Frequency Resolution | 0.024/50 Hz analog input, 0.1 Hz display unit |
Marking | CE |
Motor Starter Type | Variable Speed Drive |
Network Frequency | 47.5 to 63 Hz |
Noise Level | 59.9 dB 86/188/EEC |
Nominal Switching Frequency | 8 kHz |
Number Of Addresses | 1 to 247 |
Operating Position | Vertical +/- 10 degree |
Option Card | Communication card LonWorks |
Output Voltage | Less Than or Equal Power Supply Voltage |
Physical Interface | 2-wire RS 485 |
Pollution Degree | 3 IEC 61800-5-1 |
Product Destination | Asynchronous Motors |
Product Specific Application | Pumps and fans in HVAC |
Prospective Line Isc | 22 kA |
Range Of Product | Altivar 212 |
Specific Application | HVAC |
Speed Drive Output Frequency | 0.5 to 200 Hz |
Supply Voltage Limits | 170 to 264 V |
Switching Frequency | 6 to 16 kHz adjustable, 8 to 16 kHz with derating factor |
Torque Accuracy | +/- 15 % |
Transmission Rate | 9600 bps or 19200 bps |
Type Of Polarization | No impedance |
Motor Slip Compensation | Adjustable, Automatic whatever the load, Not available in voltage/frequency ratio motor control |
Product Weight | 27.4 Kg |
Communication Port Protocol | Apogee Fln, BACnet, LonWorks, METASYS N2, Modbus |
Insulation Resistance | Greater Than or Equal 1 MOhm 500 V DC for 1 minute |
Environmental Characteristic | Classes 3C1 IEC 60721-3-3, Classes 3S2 IEC 60721-3-3 |
Motor Power HP | 30 |
Shock Resistance | 15 gn 11 ms IEC 60068-2-27 |
Network Number of Phases | 3 Phases |
Power Dissipation | 763 W |
Motor Power | 22 kW |
Transient Overtorque | 120 % of nominal motor torque +/- 10 % 60 s |
Dielectric Strength | 2830 V DC between earth and power terminals, 4230 V DC between control and power terminals |
Line Current | 66.4 A 240 V to 80.4 A 200 V |
Isolation | Electrical Between Power and Control |
Discrete and Process Manufacturing | Building - HVAC compressor for scroll, Building - HVAC fan, Building - HVAC pump |
Depth | 214 mm |
Supply Frequency | 50 to 60 Hz - 5 to 5 % |
Power Range | 15 to 25 kW at 200 to 240 V 3 phases |
Ambient Air Temperature for Operation | -10 to 40 Deg C without derating, Greater Than 40 to 50 Deg C with derating factor |
Vibration Resistance | 1 gn 13 to 200 Hz EN/IEC 60068-2-8, 1.5 mm 3 to 13 Hz EN/IEC 60068-2-6 |
Rated Supply Voltage | 200 to 240 V - 15 to 10 % |
Local Signalling | 1 LED red DC bus energized |
Model No | ATV212HD22M3X |
Relative Humidity | 5 to 95 % without condensation IEC 60068-2-3, 5 to 95 % without dripping water IEC 60068-2-3 |
Apparent Power | 33.5 kVA 240 V |
Asynchronous motor control profile | Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo) |
Type of cable | IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC |
Electrical connection | Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES Terminal 50 mm² AWG 1/0 L1/R, L2/S, L3/T |
Tightening torque | 24 N.m 212 lb.in L1/R, L2/S, L3/T 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 A overload and short-circuit protection Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection |
Analogue input type | Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits |
Sampling duration | 2 ms +/- 0.5 ms F discrete, 2 ms +/- 0.5 ms R discrete, 2 ms +/- 0.5 ms RES discrete, 3.5 ms +/- 0.5 ms VIA analog, 22 ms +/- 0.5 ms VIB analog |
Response time | 2 ms +/- 0.5 ms FM analog, 7 ms +/- 0.5 ms FLA, FLC discrete, 7 ms +/- 0.5 ms FLB, FLC discrete, 7 ms +/- 0.5 ms RY, RC discrete |
Accuracy | +/- 0.6 % VIA for a temperature variation 60 °C +/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C |
Linearity error | +/- 0.15 % of maximum value input VIA +/- 0.15 % of maximum value input VIB +/- 0.2 % output FM |
Discrete output type | Configurable relay logic FLA, FLC NO 100000 cycles Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles |
Maximum switching current | 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R |
Discrete input type | Programmable F 24 V DC level 1 PLC 4700 Ohm Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm |
Discrete input logic | Positive logic (source) F, R, RES <= 5 V >= 11 V Negative logic (sink) F, R, RES >= 16 V <= 10 V |
Additional Information: